Improving Energy Efficiency by Utilizing Wetted Cellulose Pads in Passive Cooling Systems
Morady, Ebrahim; Soltani, Madjid; Moradi Kashkooli, Farshad; Ziabasharhagh, Masoud; Al-Haq, Armughan; Nathwani, Jatin
通讯作者Soltani, M (corresponding author),KN Toosi Univ Technol, Dept Mech Engn, Tehran 1996715433, Iran. ; Soltani, M (corresponding author),Univ Waterloo, Dept Elect & Comp Engn, Waterloo, ON N2L 3G1, Canada. ; Soltani, M (corresponding author),Univ Waterloo, Waterloo Inst Sustainable Energy WISE, Waterloo, ON N2L 3G1, Canada. ; Soltani, M (corresponding author),KN Toosi Univ Technol, Adv Energy Initiat Ctr, Tehran 1417614411, Iran.
来源期刊ENERGIES
EISSN1996-1073
出版年2022
卷号15期号:1
英文摘要The effectiveness of using wetted cellulose pads on improving the performance of two conventional passive cooling systems has been evaluated. First, an experimental design was developed to determine the impact of using a wetted cellulose pad on the temperature and velocity of the airflow. A cellulose pad (7090 model) with a cross-sectional area of 0.5 x 0.5 m(2) and three different thicknesses of 10, 15, and 30 cm were selected and tested. The results indicated that using wetted cellulose pads with thicknesses ranging from 10-30 cm decreased the outlet airflow temperature from 11.3 to 13.7 degrees C on average. For free airflow at velocity 3.5 m/s, the outlet airflow velocity from the wetted cellulose pad decreased to 0.9, 0.7 and 0.6 m/s, respectively, for cellulose pads with thicknesses of 10, 15, and 30 cm. By applying experimental results on a psychrometric chart, the humidity ratio of outlet airflow was obtained between 40-70%. The study established airflow velocity as the critical parameter in passive cooling systems. With the novel concept of combining wetted cellulose pads for passive cooling systems (i.e., wind catchers and induced ventilation), there is good potential to reduce the energy requirements for thermal comfort in buildings in regions with a hot and arid climate.
英文关键词natural ventilation passive cooling system cellulose pad wind energy wind catcher induced ventilation
类型Article
语种英语
开放获取类型gold
收录类别SCI-E
WOS记录号WOS:000758548100001
WOS关键词NATURAL VENTILATION PERFORMANCE ; WIND ; WINDCATCHER ; CONSUMPTION ; BUILDINGS ; DESIGN
WOS类目Energy & Fuels
WOS研究方向Energy & Fuels
资源类型期刊论文
条目标识符http://119.78.100.177/qdio/handle/2XILL650/376652
作者单位[Morady, Ebrahim; Soltani, Madjid; Moradi Kashkooli, Farshad; Ziabasharhagh, Masoud] KN Toosi Univ Technol, Dept Mech Engn, Tehran 1996715433, Iran; [Soltani, Madjid] Univ Waterloo, Dept Elect & Comp Engn, Waterloo, ON N2L 3G1, Canada; [Soltani, Madjid; Al-Haq, Armughan; Nathwani, Jatin] Univ Waterloo, Waterloo Inst Sustainable Energy WISE, Waterloo, ON N2L 3G1, Canada; [Soltani, Madjid] KN Toosi Univ Technol, Adv Energy Initiat Ctr, Tehran 1417614411, Iran
推荐引用方式
GB/T 7714
Morady, Ebrahim,Soltani, Madjid,Moradi Kashkooli, Farshad,et al. Improving Energy Efficiency by Utilizing Wetted Cellulose Pads in Passive Cooling Systems[J],2022,15(1).
APA Morady, Ebrahim,Soltani, Madjid,Moradi Kashkooli, Farshad,Ziabasharhagh, Masoud,Al-Haq, Armughan,&Nathwani, Jatin.(2022).Improving Energy Efficiency by Utilizing Wetted Cellulose Pads in Passive Cooling Systems.ENERGIES,15(1).
MLA Morady, Ebrahim,et al."Improving Energy Efficiency by Utilizing Wetted Cellulose Pads in Passive Cooling Systems".ENERGIES 15.1(2022).
条目包含的文件
条目无相关文件。
个性服务
推荐该条目
保存到收藏夹
导出为Endnote文件
谷歌学术
谷歌学术中相似的文章
[Morady, Ebrahim]的文章
[Soltani, Madjid]的文章
[Moradi Kashkooli, Farshad]的文章
百度学术
百度学术中相似的文章
[Morady, Ebrahim]的文章
[Soltani, Madjid]的文章
[Moradi Kashkooli, Farshad]的文章
必应学术
必应学术中相似的文章
[Morady, Ebrahim]的文章
[Soltani, Madjid]的文章
[Moradi Kashkooli, Farshad]的文章
相关权益政策
暂无数据
收藏/分享

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。