Knowledge Resource Center for Ecological Environment in Arid Area
DOI | 10.1016/j.asej.2021.03.003 |
Energy audit and evaluation of indoor environment condition inside Assiut International Airport terminal building, Egypt | |
Abdallah, Amr Sayed Hassan; Makram, Ahmed; Nayel, Mohamed Abdel-Azim | |
通讯作者 | Abdallah, ASH (corresponding author), Assiut Univ, Fac Engn, Architectural Engn Dept, Assiut 71515, Egypt. |
来源期刊 | AIN SHAMS ENGINEERING JOURNAL
![]() |
ISSN | 2090-4479 |
EISSN | 2090-4495 |
出版年 | 2021 |
卷号 | 12期号:3页码:3241-3253 |
英文摘要 | Large space buildings, such as airport terminal buildings, consume high energy due to the cooling demand; especially in hot arid climates; to achieve passenger thermal comfort. Evaluation of thermal environment and energy analysis inside airports is an important issue, in terms of reducing energy and controlling indoor environments. This work aims to analyze electrical energy consumption and the indoor environment of the terminal building at Assiut International Airport, Egypt as a case study. Indoor environmental conditions, and energy consumption with HVAC systems, were monitored inside five multiple functional zones within the terminal building (Departure hall, Public area, Duty-free hall, Gate, and Arrival hall) during summer (August 2017). The indoor environmental parameters monitored include: temperature, relative humidity, and illuminance. The results indicate the HVAC system consumed the largest portion (70%) of the overall building electricity demand, and the Energy Use Intensity (EUI) of ATZ terminal building is 300 kWh/m(2)/year. Also, indoor temperatures were found to be within the acceptable range of comfort, with a high energy consumption of 6,000,000 kWh for the year 2017. A significant reduction of monthly energy consumption was achieved based on increasing HVAC set temperature from 25 degrees C to 27 degrees C; a reduction equal to 24.5% of total energy consumption during the hot months. The results of this study help search for sustainable solutions for reducing energy consumption and improving passenger thermal comfort inside the terminal building (phase 2). (C) 2021 THE AUTHORS. Published by Elsevier BV on behalf of Faculty of Engineering, Ain Shams University. |
英文关键词 | Indoor environment Terminal building Thermal comfort Electrical energy consumption Thermal image Illuminance |
类型 | Article |
语种 | 英语 |
开放获取类型 | gold |
收录类别 | SCI-E |
WOS记录号 | WOS:000701742600012 |
WOS关键词 | CONSUMPTION ; QUALITY |
WOS类目 | Engineering, Multidisciplinary |
WOS研究方向 | Engineering |
资源类型 | 期刊论文 |
条目标识符 | http://119.78.100.177/qdio/handle/2XILL650/362431 |
作者单位 | [Abdallah, Amr Sayed Hassan] Assiut Univ, Fac Engn, Architectural Engn Dept, Assiut 71515, Egypt; [Makram, Ahmed] Assuit Int Airport, Assiut, Egypt; [Nayel, Mohamed Abdel-Azim] Assiut Univ, Fac Engn, Elect Engn Dept, Assiut 71518, Egypt |
推荐引用方式 GB/T 7714 | Abdallah, Amr Sayed Hassan,Makram, Ahmed,Nayel, Mohamed Abdel-Azim. Energy audit and evaluation of indoor environment condition inside Assiut International Airport terminal building, Egypt[J],2021,12(3):3241-3253. |
APA | Abdallah, Amr Sayed Hassan,Makram, Ahmed,&Nayel, Mohamed Abdel-Azim.(2021).Energy audit and evaluation of indoor environment condition inside Assiut International Airport terminal building, Egypt.AIN SHAMS ENGINEERING JOURNAL,12(3),3241-3253. |
MLA | Abdallah, Amr Sayed Hassan,et al."Energy audit and evaluation of indoor environment condition inside Assiut International Airport terminal building, Egypt".AIN SHAMS ENGINEERING JOURNAL 12.3(2021):3241-3253. |
条目包含的文件 | 条目无相关文件。 |