英文摘要Choosing the right control strategies is an important task for effective operation of variable air volume reheat (VAVR) system in commercial buildings. In this design, dampers position inside air terminal units (ATUs) are modulated to adjust the amount of air supply volume based on thermal zones cooling or heating demand. A minimum air flow fraction (MAFF) is set for damper settings of ATUs to avoid under-ventilation problem in thermal zones. This study investigated the impact of MAFF value on various performance aspects of multiple-zone VAVR design in different building applications and climate types. A five-storey commercial building for three applications of school, office and retail in four climate types of tropical monsoon, hot desert, Mediterranean and humid continental have been simulated in EnergyPlus building simulation software. The results of simulations have shown that lowering MAFF value in ATUs would reduce the required reheat coil energy to maintain precise air supply temperature at part load cooling scenarios. Nonetheless, this reduction could have some implications on thermal comfort and indoor air quality level of thermal zones in a multiple-zone arrangement. It was concluded that in general it is an energy efficient control strategy to keep MAFF value to as low as 0.1 for high ventilation rate spaces like classrooms in school buildings (except for hot desert climate). On the other hand, it is advisable to not reduce MAFF value below 0.3 for low ventilation rate spaces like office areas to avoid any air quality issues in thermal zones.
英文关键词damper control settings variable air volume reheat air terminal unit minimum air flow fraction building simulation EnergyPlus
类型Article
语种英语
开放获取类型Green Accepted
收录类别CSCD
WOS研究方向Architecture
CSCD记录号CSCD:6113938
资源类型期刊论文
条目标识符http://119.78.100.177/qdio/handle/2XILL650/335881
作者单位Saber Esmail M, Department of Civil and Structural Engineering, University of Sheffield, Mappin Street, Sheffield, S1 3JD, England.
推荐引用方式
GB/T 7714
Saber Esmail M. Performance evaluation of damper control settings for operation of multiple-zone variable air volume reheat system in different building applications and climate types[J],2017,10(5):687-696.
APA Saber Esmail M.(2017).Performance evaluation of damper control settings for operation of multiple-zone variable air volume reheat system in different building applications and climate types.Building Simulation,10(5),687-696.
MLA Saber Esmail M."Performance evaluation of damper control settings for operation of multiple-zone variable air volume reheat system in different building applications and climate types".Building Simulation 10.5(2017):687-696.
条目包含的文件
条目无相关文件。
个性服务
推荐该条目
保存到收藏夹
导出为Endnote文件
谷歌学术
谷歌学术中相似的文章
[Saber Esmail M]的文章
百度学术
百度学术中相似的文章
[Saber Esmail M]的文章
必应学术
必应学术中相似的文章
[Saber Esmail M]的文章
相关权益政策
暂无数据
收藏/分享

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。