Knowledge Resource Center for Ecological Environment in Arid Area
DOI | 10.1007/978-981-13-1405-6_76 |
Experimental Study of Fouling in Hybrid Cooling Tower Used in CSP Plants: A Prototype Scale Preliminary Test Feedback | |
Zaza, Afaf1,2; Eddine Laadel, Nour2; Agalit, Hassan2; Bennouna, El Ghali2; El Hammami, Youness1 | |
通讯作者 | Zaza, Afaf |
会议名称 | 1st International Conference on Electronic Engineering and Renewable Energy (ICEERE) |
会议日期 | APR 15-17, 2018 |
会议地点 | Saidia, MOROCCO |
英文摘要 | Concentrated solar power (CSP) is a promising technology to secure the globe energetic future. However, the high cooling water consumption of CSP plants presents a big challenge against its viability in the energy market, especially in arid regions. To resolve this issue, hybrid dry-wet cooling systems are investigated to enhance the low efficiency of dry cooling systems from one side, and to reduce water consumption of wet cooling systems from the other side. Nowadays, the negative impacts of fouling problem in these hybrid systems on its performances aren't well documented in the available scientific data. Thus in this scope, the main aim of this paper is to fulfill this lack of knowledge in literature by experimental study of the effect of water quality on fouling rate in hybrid cooling tower designed for the CSP plants. For this purpose, a prototype scale unit of this system was installed in the Green Energy Park research platform, which is located in Benguerir, Morocco; and a preliminary test cycle was carried out for several days to verify the reliability of this novel test rig for the programed future tests in MinWater CSP project. Thus, by analyzing the collected measurements about the different performance indicators (e.g. fouling resistance, the exchanged heat, etc.), it is concluded that the fouling resistance measurements for the galvanized tube (R = 100%) are more significant compared to those recorded for the polymer one (R = 6.83%). Moreover, the obtained results are generally in coherence with the expected physical behaviors reported in literature. |
英文关键词 | Fouling Water quality Hybrid-cooling tower Preliminary test |
来源出版物 | PROCEEDINGS OF THE 1ST INTERNATIONAL CONFERENCE ON ELECTRONIC ENGINEERING AND RENEWABLE ENERGY, ICEERE 2018 |
ISSN | 1876-1100 |
EISSN | 1876-1119 |
出版年 | 2019 |
卷号 | 519 |
页码 | 664-671 |
ISBN | 978-981-13-1404-9 |
EISBN | 978-981-13-1405-6 |
出版者 | SPRINGER |
类型 | Proceedings Paper |
语种 | 英语 |
国家 | Morocco |
收录类别 | CPCI-S |
WOS记录号 | WOS:000460955000076 |
WOS类目 | Energy & Fuels ; Engineering, Electrical & Electronic |
WOS研究方向 | Energy & Fuels ; Engineering |
资源类型 | 会议论文 |
条目标识符 | http://119.78.100.177/qdio/handle/2XILL650/308021 |
作者单位 | 1.Ibno Zohr Univ, ENSA, Natl Sch Appl Sci, Lab Mech Proc Energy & Environm, Agadir, Morocco; 2.IRESEN, Thermal Syst Dept, 16 Rue Amir Sidi Mohamed Souissi, Rabat, Morocco |
推荐引用方式 GB/T 7714 | Zaza, Afaf,Eddine Laadel, Nour,Agalit, Hassan,et al. Experimental Study of Fouling in Hybrid Cooling Tower Used in CSP Plants: A Prototype Scale Preliminary Test Feedback[C]:SPRINGER,2019:664-671. |
条目包含的文件 | 条目无相关文件。 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。