英文摘要 | Conductors for most buildings in the United States are sized using the National Electrical Code (NEC). The 2014 NEC now requires that a value be added to the ambient temperature used to determine the ampacity of conductors installed on rooftops. This paper reports the results of a related experimental test (on both energized and non-energized cables) that is conducted on a rooftop of a building located in the desert southwest during the hottest period of the year. The recorded temperature rise of the conductors tested is compared to the temperature adders specified in the Code. The maximum recorded temperature of the energized conductors is also compared to the rated temperature of the conductor insulation. |
英文关键词 | Conductor sizing temperature rise roof-mounted conduits National Electric Code (NEC) |
来源出版物 | 2015 IEEE POWER & ENERGY SOCIETY GENERAL MEETING |
ISSN | 1944-9925 |
出版年 | 2015 |
EISBN | 978-1-4673-8040-9 |
出版者 | IEEE |
类型 | Proceedings Paper |
语种 | 英语 |
国家 | USA |
收录类别 | CPCI-S |
WOS记录号 | WOS:000371397502093 |
WOS类目 | Energy & Fuels ; Engineering, Electrical & Electronic |
WOS研究方向 | Energy & Fuels ; Engineering |
资源类型 | 会议论文 |
条目标识符 | http://119.78.100.177/qdio/handle/2XILL650/304384 |
作者单位 | 1.Univ Nevada, Dept Elect Engn, Las Vegas, NV 89154 USA; 2.Univ Nevada, Energy Res Ctr, Las Vegas, NV 89154 USA |
推荐引用方式 GB/T 7714 | Mohammad, Z.,Baghzouz, Y.,Hurt, R.. Experimental Test on Temperature Rise of Conductors in Roof-Mounted Conduits[C]:IEEE,2015. |
条目包含的文件 | 条目无相关文件。 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。