Knowledge Resource Center for Ecological Environment in Arid Area
DOI | 10.2172/206515 |
报告编号 | WHC-EP--0873 |
来源ID | OSTI_ID: 206515 |
Engineering evaluation of alternatives: Managing the assumed leak from single-shell Tank 241-T-101 | |
Brevick, C.H. [ICF Kaiser Hanford Co., Richland, WA (United States)]; Jenkins, C. [Westinghouse Hanford Co., Richland, WA (United States)] | |
英文摘要 | At mid-year 1992, the liquid level gage for Tank 241-T-101 indicated that 6,000 to 9,000 gal had leaked. Because of the liquid level anomaly, Tank 241-T-101 was declared an assumed leaker on October 4, 1992. SSTs liquid level gages have been historically unreliable. False readings can occur because of instrument failures, floating salt cake, and salt encrustation. Gages frequently self-correct and tanks show no indication of leak. Tank levels cannot be visually inspected and verified because of high radiation fields. The gage in Tank 241-T-101 has largely corrected itself since the mid-year 1992 reading. Therefore, doubt exists that a leak has occurred, or that the magnitude of the leak poses any immediate environmental threat. While reluctance exists to use valuable DST space unnecessarily, there is a large safety and economic incentive to prevent or mitigate release of tank liquid waste into the surrounding environment. During the assessment of the significance of the Tank 241-T-101 liquid level gage readings, Washington State Department of Ecology determined that Westinghouse Hanford Company was not in compliance with regulatory requirements, and directed transfer of the Tank 241-T-101 liquid contents into a DST. Meanwhile, DOE directed WHC to examine reasonable alternatives/options for safe interim management of Tank 241-T-101 wastes before taking action. The five alternatives that could be used to manage waste from a leaking SST are: (1) No-Action, (2) In-Tank Stabilization, (3) External Tank Stabilization, (4) Liquid Retrieval, and (5) Total Retrieval. The findings of these examinations are reported in this study. |
出版年 | 1996 |
报告类型 | Technical Report |
语种 | 英语 |
国家 | 美国 |
来源学科分类 | 05 NUCLEAR FUELS ; HANFORD RESERVATION ; RADIOACTIVE WASTE STORAGE ; STORAGE FACILITIES ; LEAKS ; REMEDIAL ACTION ; PLANNING ; LEVEL INDICATORS ; ACCURACY ; STABILIZATION ; WASTE RETRIEVAL ; COMPARATIVE EVALUATIONS |
URL | http://www.osti.gov/scitech/servlets/purl/206515 |
资源类型 | 科技报告 |
条目标识符 | http://119.78.100.177/qdio/handle/2XILL650/266482 |
推荐引用方式 GB/T 7714 | Brevick, C.H. [ICF Kaiser Hanford Co., Richland, WA ,Jenkins, C. [Westinghouse Hanford Co., Richland, WA . Engineering evaluation of alternatives: Managing the assumed leak from single-shell Tank 241-T-101,1996. |
条目包含的文件 | 条目无相关文件。 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。