Development of a new pole-slip protection function for synchronous machines / Lafras Lamont | |
Lamont;Lafras | |
出版年 | 2011 |
学位授予单位 | North-West University |
英文摘要 | The rotor shaft of a synchronous machine can experience severe mechanical stress due to torque pulsations during a pole-slip condition. All pole-slip protection relays currently on the market use the impedance pole-slip protection method to detect a pole-slip. No commercial relay currently available can predict accurately when a generator is about to experience a damaging pole-slip. All the relays will only trip a generator after it has pole-slipped one or more times. Severe mechanical damage could be caused to a machine after only one pole-slip. It is therefore essential to enhance pole-slip protection relays to such an extent that it can trip a generator before it pole slips. The proposed pole-slip protection function must predict when a generator will become unstable during a network fault. As soon as instability is predicted, the generator must be tripped before the fault is cleared to avoid damaging post-fault torque effects. Conventional impedance pole-slip protection methods are are also discussed and the shortcomings of impedance pole-slip protection are investigated. The new pole-slip protection function was designed by using PSCAD. Detailed PSCAD simulations on different network configurations proved that the new pole-slip protection function will trip a generator before a damaging pole-slip occurs. The new pole-slip protection function was also implemented on an ABB REM543 multifunctional protection relay and tested on a RTDS. The concept of the new pole-slip function was successfully demonstrated on the protection relay. The operation of conventional impedance scheme relays was compared with the proposed pole-slip function for different fault conditions. Although the new pole-slip protection function is more complex than the existing impedance functions, it was concluded that similar skills are required to test and commission the new protection function. The new pole-slip function outperforms the impedance protection methods, since the new protection function can trip the generator before it pole-slips. PhD (Electrical Engineering), North-West University, Potchefstroom Campus, 2011 |
英文关键词 | Synchronous generators Pole-slip protection Out-of-step Power system stability Powerswing Equal area criteria Impedance protection |
语种 | 英语 |
URL | http://hdl.handle.net/10394/9730 |
来源机构 | North-West University |
资源类型 | 学位论文 |
条目标识符 | http://119.78.100.177/qdio/handle/2XILL650/246027 |
推荐引用方式 GB/T 7714 | Lamont;Lafras. Development of a new pole-slip protection function for synchronous machines / Lafras Lamont[D]. North-West University,2011. |
条目包含的文件 | 条目无相关文件。 |
个性服务 |
推荐该条目 |
保存到收藏夹 |
导出为Endnote文件 |
谷歌学术 |
谷歌学术中相似的文章 |
[Lamont;Lafras]的文章 |
百度学术 |
百度学术中相似的文章 |
[Lamont;Lafras]的文章 |
必应学术 |
必应学术中相似的文章 |
[Lamont;Lafras]的文章 |
相关权益政策 |
暂无数据 |
收藏/分享 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。