Hong, Tianzhen; Fisk, William J. | |
通讯作者 | Hong, Tianzhen |
来源期刊 | BUILDING SIMULATION
![]() |
ISSN | 1996-3599 |
出版年 | 2010 |
卷号 | 3期号:2页码:117-124 |
英文摘要 | A prototypical office building meeting the prescriptive requirements of the 2008 California Building Energy Efficiency Standards (Title 24) was used in EnergyPlus simulations to calculate the energy savings potential of demand controlled ventilation (DCV) in five typical California climates per three design occupancy densities and two minimum ventilation rates. The assumed minimum ventilation rates in offices without DCV, based on two different measurement methods employed in a large survey, were 38 and 13 L/s per occupant. The results of the life cycle cost analysis show DCV is cost effective for office spaces if the typical minimum ventilation rate without DCV is 38 L/s per person, except at the low design occupancy of 10.8 people per 100 m(2) in climate zones 3 (north coast) and 6 (south coast). DCV was not found to be cost effective if the typical minimum ventilation rate without DCV is 13 L/s per occupant, except at high design occupancy of 21.5 people per 100 m(2) in climate zones 14 (desert) and 16 (mountains). Until the large uncertainties about the base case ventilation rates in offices without DCV are reduced, the case for requiring DCV in general office spaces will be a weak case. Under the Title 24 standard office occupant density of 10.8 people per 100 m(2), DCV becomes cost effective when the base case minimum ventilation rate is greater than 42.5, 43.0, 24.0, 19.0, and 18.0 L/s per person for climate zones 3, 6, 12, 14, and 16, respectively. |
英文关键词 | building simulation building energy standard demand controlled ventilation energy savings |
类型 | Article |
语种 | 英语 |
国家 | USA |
收录类别 | SCI-E |
WOS记录号 | WOS:000289290900003 |
WOS类目 | Thermodynamics ; Construction & Building Technology |
WOS研究方向 | Thermodynamics ; Construction & Building Technology |
来源机构 | University of California, Berkeley |
资源类型 | 期刊论文 |
条目标识符 | http://119.78.100.177/qdio/handle/2XILL650/163571 |
作者单位 | Univ Calif Berkeley, Lawrence Berkeley Lab, Environm Energy Technol Div, Berkeley, CA 94720 USA |
推荐引用方式 GB/T 7714 | Hong, Tianzhen,Fisk, William J.. Assessment of energy savings potential from the use of demand controlled ventilation in general office spaces in California[J]. University of California, Berkeley,2010,3(2):117-124. |
APA | Hong, Tianzhen,&Fisk, William J..(2010).Assessment of energy savings potential from the use of demand controlled ventilation in general office spaces in California.BUILDING SIMULATION,3(2),117-124. |
MLA | Hong, Tianzhen,et al."Assessment of energy savings potential from the use of demand controlled ventilation in general office spaces in California".BUILDING SIMULATION 3.2(2010):117-124. |