英文摘要

Since its first introduction to the market in the 1970s, cooling tower film fill technology has significantly increased thermal performance and reduced the size of cooling towers. However, the narrow spaces between film fill sheets make them more susceptible to fouling. Without proper chemical treatment, deposits can accumulate within the film fill resulting in reduced tower efficiency, increased fouling and plugging of the fill. These phenomena could eventually lead to collapse of the tower structure. This paper describes a new approach to remedy the high efficiency film fill fouling problem in a geothermal power plant. The plant has a long history of fill fouling problems due to complex make-up water chemistry and desert-related environmental conditions. In recent years, various biocide and biodispersant treatments have significantly improved fouling control by slowing down tower fill deposition rates. However, no program has been successful in reducing fill weight gain, especially during the summer months. Within six weeks after starting a new control program, the average weight of the tower fill deposits dropped 22% and thermal performance of the cooling tower increased 20%. The treatment resulted in significant improvements in cooling tower operation and power generation efficiency.


英文关键词film fill cooling tower biofouling biocide biodispersant biodetergent thermal efficiency
类型Article
语种英语
国家USA
收录类别SCI-E
WOS记录号WOS:000082487100004
WOS类目Electrochemistry ; Metallurgy & Metallurgical Engineering ; Materials Science, Coatings & Films
WOS研究方向Electrochemistry ; Metallurgy & Metallurgical Engineering ; Materials Science
资源类型期刊论文
条目标识符http://119.78.100.177/qdio/handle/2XILL650/137173
作者单位(1)Nalco Chem Co, Nalco Ctr 1, Naperville, IL 60563 USA
推荐引用方式
GB/T 7714
Yu, FP,Ginn, LD,McCoy, WF. Cooling tower fill fouling control in a geothermal power plant[J],1999,17(3-4):205-217.
APA Yu, FP,Ginn, LD,&McCoy, WF.(1999).Cooling tower fill fouling control in a geothermal power plant.CORROSION REVIEWS,17(3-4),205-217.
MLA Yu, FP,et al."Cooling tower fill fouling control in a geothermal power plant".CORROSION REVIEWS 17.3-4(1999):205-217.
条目包含的文件
条目无相关文件。
个性服务
推荐该条目
保存到收藏夹
导出为Endnote文件
谷歌学术
谷歌学术中相似的文章
[Yu, FP]的文章
[Ginn, LD]的文章
[McCoy, WF]的文章
百度学术
百度学术中相似的文章
[Yu, FP]的文章
[Ginn, LD]的文章
[McCoy, WF]的文章
必应学术
必应学术中相似的文章
[Yu, FP]的文章
[Ginn, LD]的文章
[McCoy, WF]的文章
相关权益政策
暂无数据
收藏/分享

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。